Retrofitted systems
Most modern refrigeration systems went into existing buildings. The plant room was never designed as a machinery room — the refrigeration replacement made it one, but the room itself was often never brought up to standard.
EN 378 · Machinery room survey
EN 378 compliance survey of refrigeration machinery rooms and refrigerant systems — emergency ventilation, gas detection, charge/volume checks — and the design of remediation for any deficiencies found. Fixed-fee survey and compliance report, based in Budapest, serving all of Hungary.
The problem
Most modern refrigeration systems went into existing buildings. The plant room was never designed as a machinery room — the refrigeration replacement made it one, but the room itself was often never brought up to standard.
CO₂ is not a fluorinated greenhouse gas, so it is outside the leak-check and record-keeping obligations of the F-gas Regulation (EU 517/2014). The regular, documented external inspections that would eventually surface deficiencies in HFC systems simply do not happen.
Transcritical CO₂ systems operate with large charges of a heavy gas in typically small machinery rooms. In case of a leak the gas accumulates near the floor — emergency ventilation and gas detection are not a formality.
The remedy is also site-specific: whether an existing ventilation riser can be reused or a new shaft must be opened makes an order-of-magnitude cost difference. It cannot be judged from the desk — it can from a survey.
The same logic applies to VRF systems: the ratio of refrigerant charge to the volume of the smallest occupied room (practical limit) is regularly exceeded in offices, hotels and meeting rooms — and with A2L refrigerants (e.g. R32) flammability requirements apply as well.
Who it is for
Operations and investment teams (grocery, discount, fuel-station shops). A repeatable survey with uniform methodology and documentation across multiple sites.
Documented coverage of the compliance risk under an operating contract — the compliance report is a tool for managing operator liability.
As a mechanical / ventilation design subcontractor: from survey to detailed design, with construction supervision.
Charge / room-volume verification of VRF and split systems — meeting rooms, hotel rooms and other small-volume spaces are most frequently affected.
How we work
Step 2 is valuable on its own: the compliance report tells you where you stand, and you can plan with it — without committing to the full design up front.
Machinery room geometry, refrigerant charge, equipment nameplates, existing gas detection and ventilation, ductwork opportunities, photo documentation.
→ Survey report
Charge / room-volume checks, machinery room classification, itemised verification of the requirements of MSZ EN 378-3.
→ Compliance report — what is missing, and how large the gap is
Technically and financially realistic options, making use of existing site conditions (e.g. existing ventilation risers).
→ Concept design with order-of-magnitude cost estimate
Sizing, equipment selection, controls, bill of quantities — documentation ready for contractor tendering.
→ Technical specification + unpriced bill of quantities
Designer's site supervision, verification of commissioning and functional tests, as-built documentation.
→ Handover / as-built documentation
Steps 1–3 form the fixed-fee base product. If you decide to proceed, we quote the detailed design separately, and accompany the construction with designer's supervision — closing with as-built documentation.
What you receive
Systems covered
Machinery rooms of grocery stores and discount chains. Large charge, small floor area, heavy gas — emergency ventilation and gas detection are most critical here.
Office buildings, hotels. The ratio of refrigerant charge to the volume of the smallest occupied room (practical limit) is regularly exceeded; with R32 (A2L) flammability requirements also apply.
Machinery rooms and refrigerated spaces of cold stores, food-industry plants and logistics centres — ammonia (B2L) systems together with a specialist partner.
Siting and ventilation requirements of propane (R290, A3) and other flammable-refrigerant equipment according to the EN 378 safety classification.
Fee calculator
On-site survey + compliance assessment (compliance report) + preliminary remediation concept, for one machinery room. Based in Budapest; the travel fee is calculated from the site's postal code, for the round trip.
Please enter a valid Hungarian postal code (4 digits).
Net, indicative price; VAT not included. The travel fee includes vehicle costs and the engineering fee for travel time, with the route estimated at average speed. A firm, binding offer is sent by e-mail. For multiple machinery rooms or sites we provide an individual package offer at a discount.
Request a quote for this siteFAQ
Most modern high-charge systems (transcritical CO₂, VRF) were retrofitted into existing buildings, and the machinery room itself was often never brought up to standard. The deficiency causes no malfunction — the system cools perfectly — so it never surfaces on its own. It only shows up in a survey, and it is better if that survey is a planned one rather than an incident.
EN 378 is a standard, not a law, so there is no direct "EN 378 fine". The obligation applies indirectly: through employer health-and-safety duties, national fire-safety regulations, the responsibility of the installer and the operator, and contractual and insurance conditions. The absence of a standard-compliant installation is a risk that falls within the responsibility of the employer and the operator — the compliance report is the documented management of that risk.
Surveying one machinery room typically takes 2–3 hours on site, with one engineer. Store operation is not disturbed: we work in the machinery room and along the ventilation routes; at most a short walk-through of the sales area is needed.
No. The survey is carried out without opening the operating system: geometry, nameplates, existing detection and ventilation, photo documentation. There is no intervention.
The survey and assessment fee is fixed and can be calculated in advance with the calculator above. The cost of remediation, however, is site-specific: whether an existing ventilation riser can be reused or a new shaft must be opened makes an order-of-magnitude difference. That is why step 3 provides an order-of-magnitude estimate for the decision, and firm construction prices come from contractor bids on the unpriced bill of quantities.
Then you receive a compliance report stating exactly that — documenting that the installation is operated in line with the requirements of the standard. In insurance, leasing and audit situations this is valuable in itself, and it closes the liability question.
Yes — this service was built for that: for multi-site chains we work with a uniform methodology and identically structured reports, making risk comparable across the portfolio. For multiple sites we provide an individual package offer at a discount — request a quote using the form.